Electrical Cable AC90 2 C 14 AWG 600 V 300 m AC2C14X300

WIRE-AC2C14X300 MFG #: AC2C14X300
  • Armor Material: Aluminum
  • Best Seller: No
  • Brand: NEXANS
  • CMEQ: CAB14/2AC90;CAB14/2AC90300;14/2BX
  • Conductor Material: Copper
  • Dangerous Goods: No
  • Diameter: 0.47" (11.938 mm)
  • Direct Burial: No
  • Discontinued: No
  • Featured Product: No
  • Flame Spread Rating: FT4
  • Green Product: No
  • Inner Insulation Material: Polyethylene
  • Length: 300 m
  • Limited Quantity: No
  • Made in Canada: No
  • Manufacturer: WIRE
  • Manufacturer Category: AC90 PRICED WEEKLY
  • Maximum Operating Temperature: 90
  • Maximum Operating Voltage: 600
  • Mfr Vendor ID: 554
  • Minimum Operating Temperature: -40
  • Number of Conductors: 2
  • Overhead Installation: No
  • Oversize product: Yes
  • Packing Type: Reel
  • Product Manufacturer Number: 12000493
  • Restricted Delivery: Yes
  • Special Attributes: Oversize Product, Restricted Delivery
  • SPF Product ID: 762189
  • Standards: CSA
  • Unit of Measure: M
  • UPC: 97021000012
  • Web Group: 1100100000000
  • Wet Location: No
  • Wire And Cable Type: AC90
  • Wire Gauge: 14
ARMOURED CABLE FOR COMMERCIAL, INDUSTRIAL & APARTMENT USE

CSA File #LL23462 Class 5811 01
Two copper conductor material (ACM) conductors with low temperature EXELENE* cross-linked polyethylene insulation (RW90 XLPE) and
bare copper bonding wire. Conductor assembly paper wrapped and covered with bare interlocked aluminum armour. Rated 600 volts. LEAD FREE
and RoHS compliant. Limited Smoke Zero Halogen - CSA rated ST1 per CSA 22.2 No. 2556. Meets the FT4 flame spread test.

Application
For open and concealed wiring in dry locations only.
For use in cabletroughs and ventilated flexible cableways in dry locations only.
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C. Approved for use with ceiling fixtures.

Construction characteristics
Conductor material Copper

Electrical characteristics
Maximum operating voltage 600 V

Usage characteristics
Maximum operating temperature 90 °C